Desenvolvimento de um sistema para detecção de falhas de alta impedancia em redes de distribuição
AUTOR(ES)
Patricia Romeiro da Silva Jota
DATA DE PUBLICAÇÃO
1996
RESUMO
In this thesis, the development of a methodology for detection of High Impedance Faults in primary distribution feeders is presented. The technique used is based on the feeder response to a short pulse signal periodicaly injected at the substation outlet. The response to each pulse is compared to the ones previously stored in a database. The database contains the feeder response to the known normal operating configurations. It is assumed that if the response does not coincide with any of the stored responses, then the feeder is operating in a faulty condition. Three different techniques have been implemented and tested using data collected from a real feeder of Campanhia Energetica de Minas Gerais (CEMIG), at Caratinga city, State of Minas Gerais (MG), Brazil... Note: The complete abstract is available with the full electronic digital thesis or dissertations
ASSUNTO(S)
sistemas digitais sistemas de energia eletrica - proteção energia eletrica - distribuição falha de sistema (engenharia) inteligencia artificial
ACESSO AO ARTIGO
http://libdigi.unicamp.br/document/?code=vtls000108208Documentos Relacionados
- Detecção de falhas em um reator de pirolise de etano : desenvolvimento de um sistema baseado em redes neurais artificiais
- Faltas de alta impedância: detecção e localização de rompimento de condutores em circuito primário de redes aéreas de distribuição baseado em desequilibrio de tensão
- Proposition of a system for simulation of high impedance faults in distribuition networks.
- Técnica alternativa para detecção de faltas de alta impedância
- Desenvolvimento de um sistema automatizado para medição de impedância elétrica