Efficacy of ozone in eradication of Legionella pneumophila from hospital plumbing fixtures.
AUTOR(ES)
Edelstein, P H
RESUMO
The effect of ozonation of supply water for one wing of an unoccupied hospital building which had positive cultures for Legionella pneumophila from multiple potable water fixtures was studied in a prospective, controlled fashion. Mean ozone residual concentrations of 0.79 mg/liter eradicated L. pneumophila from the fixtures, but so did nonozonated water in the control wing fixtures. The efficacy of the nonozonated water was most probably due to a mechanical flushing effect and to an unexpected rise in the chlorine content of the supply water. Determination of the in vitro activity of ozone against L. pneumophila did not predict the efficacy of its eradication from water fixtures treated with ozone.
ACESSO AO ARTIGO
http://www.pubmedcentral.nih.gov/articlerender.fcgi?artid=242192Documentos Relacionados
- Hot water systems as sources of Legionella pneumophila in hospital and nonhospital plumbing fixtures.
- Role of stagnation and obstruction of water flow in isolation of Legionella pneumophila from hospital plumbing.
- Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system.
- Effects of metals on Legionella pneumophila growth in drinking water plumbing systems.
- Influence of Plumbing Materials on Biofilm Formation and Growth of Legionella pneumophila in Potable Water Systems